What is a Shear Wall Building?
Reinforced concrete (RC) buildings often have vertical plate-like RC walls called Shear Walls (Figure 1) in addition to slabs, beams and columns. These walls generally start at foundation level and are continuous throughout the building height. Their thickness can be as low as 150mm, or as high as 400mm in high rise buildings. Shear walls are usually provided along both length and width of buildings (Figure 1). Shear walls are like vertically-oriented wide beams that carry earthquake loads downwards to the foundation.
Advantages of Shear Walls in RC Buildings
Properly designed and detailed buildings with shear walls have shown very good performance in past earthquakes. The overwhelming success of buildings with shear walls in resisting strong earthquakes is summarised in the quote:
“We cannot afford to build concrete buildings meant to resist severe earthquakes without shear walls.” by Mark Fintel, a noted consulting engineer in USA
Shear walls in high seismic regions require special detailing. However, in past earthquakes, even buildings with sufficient amount of walls that were not specially detailed for seismic performance (but had enough well-distributed reinforcement) were saved from collapse. Shear wall buildings are a popular choice in many earthquake prone countries, like Chile, New Zealand and USA. Shear walls are easy to construct, because reinforcement detailing of walls is relatively straight-forward and therefore easily implemented at site. Shear walls are efficient, both in terms of construction cost and effectiveness in minimizing earthquake damage in structural and nonstructural elements (like glass windows and building contents).
Architectural Aspects of Shear Walls
Most RC buildings with shear walls also have columns; these columns primarily carry gravity loads (i.e., those due to self-weight and contents of building).
Shear walls provide large strength and stiffness to buildings in the direction of their orientation, which significantly reduces lateral sway of the building and thereby reduces damage to structure and its contents. Since shear walls carry large horizontal earthquake forces, the overturning effects on them are large. Thus, design of their foundations requires special attention. Shear walls should be provided along preferably both length and width. However, if they are provided along only one direction, a proper grid of beams and columns in the vertical plane (called a moment-resistant frame) must be provided along the other direction to resist strong earthquake effects.
Door or window openings can be provided in shear walls, but their size must be small to ensure least interruption to force flow through walls. Moreover, openings should be symmetrically located. Special design checks are required to ensure that the net cross-sectional area of a wall at an opening is sufficient to carry the horizontal earthquake force.
Shear walls in buildings must be symmetrically located in plan to reduce ill-effects of twist in buildings (Figure 2). They could be placed symmetrically along one or both directions in plan. Shear walls are more effective when located along exterior perimeter of the building – such a layout increases resistance of the building to twisting.
Ductile Design of Shear Walls
Just like reinforced concrete (RC) beams and columns, RC shear walls also perform much better if designed to be ductile. Overall geometric proportions of the wall, types and amount of reinforcement, and connection with remaining elements in the building help in improving the ductility of walls. The Indian Standard Ductile Detailing Code for RC members (IS: 13920-1993) provides special design guidelines for ductile detailing of shear walls.
Overall Geometry of Walls
Shear walls are oblong in cross-section, i.e., one dimension of the cross-section is much larger than the other. While rectangular cross-section is common, L- and U-shaped sections are also used (Figure 3). Thin-walled hollow RC shafts around the elevator core of buildings also act as shear walls, and should be taken advantage of to resist earthquake forces.
Reinforcement Bars in RC Walls
Steel reinforcing bars are to be provided in walls in regularly spaced vertical and horizontal grids (Figure 4a). The vertical and horizontal reinforcement in the wall can be placed in one or two parallel layers called curtains. Horizontal reinforcement needs to be anchored at the ends of walls. The minimum area of reinforcing steel to be provided is 0.0025 times the cross-sectional area, along each of the horizontal and vertical directions. This vertical reinforcement should be distributed uniformly across the wall cross-section.
Boundary Elements
Under the large overturning effects caused by horizontal earthquake forces, edges of shear walls experience high compressive and tensile stresses. To ensure that shear walls behave in a ductile way, concrete in the wall end regions must be reinforced in a special manner to sustain these load reversals without loosing strength (Figure 4b). End regions of a wall with increased confinement are called boundary elements. This special confining transverse reinforcement in boundary elements is similar to that provided in columns of RC frames. Sometimes, the thickness of the shear wall in these boundary elements is also increased. RC walls with boundary elements have substantially higher bending strength and horizontal shear force carrying capacity, and are therefore less susceptible to earthquake damage than walls without boundary elements.
Reading Material
IS 13920, (1993), “Indian Standard Code of Practice for Ductile Detailing of Reinforced Concrete Structures Subjected to Seismic Forces,” Bureau of Indian Standards, New Delhi
Paulay,T., and Priestley,M.J.N., (1992), “Seismic Design of Reinforced Concrete and Masonry Buildings,” John Wiley & Sons, USA
Authored by:
C.V.R. Murty, Indian Institute of Technology Kanpur, Kanpur, India
Sponsored by:
Building Materials and Technology Promotion Council, New Delhi, India (www.bmtpc.org)